SF6 Gas Insulated Sectionalizer

The SF6 gas insulated sectionalizer is designed for a self-contained, circuit-opening device used in conjunction with source-side protective devices, such as reclosers or cicuit breakers, to automatically isolate faulted sections of electrical distribution systems.

FEATURE
  • Maintenance free
  • Light weight and easy installation
  • Inrush current restraint
  • Safety devices(low pressure interlocking, pressure relief, locking)
ADVANTAGES
  • It can be applied between two protective devices having operating curves, which are close together. This is a vital feature in a location where an additional step in coordination is not practical or possible.
  • It can be used on close-in taps where high available fault current prevents coordination with fuses.
  • It has fault close and latch capability for any fault-closing operations.
SPECIFICATIONS
SPECIFICATIONS detail
Rated voltage(kV) 12(15) 24(25.8) 36(38)
Rated current(A) 200 / 400 / 630 200 / 400 / 630 200 / 400 / 630
Rated power frequency withstand voltage(kV) 50 60 70
Rated lightning impulse withstand voltage(kV) 110 150 170
Rated short circuit making current(kA, peak) 25 / 32.5 25 / 32.5 25 / 32.5
Rated short-time current(kA, RMS) 1s 10 / 12.5 10 / 12.5 10 / 12.5
10s 3.5 3.5 3.5
Minimum actuating current(A) Phase 10 ~ 900
Ground 2 ~ 900
Inrush restraint multiplier 1.0 ~ 10.0
Mechanical endurance(times) 5,000 5,000 5,000